INTRODUCTION
Transformer is one of the most important but complex component of electricity transmission and distribution system. Much attention is needed on maintenance of transformers in order to have fault free electric supply and to maximize the lifetime and efficacy of a transformer. Thus, it is important to be aware of possible faults that may occur. It is equally important to know how to detect them early. Regular monitoring and maintenance can make it possible to detect new flaws before much damage occur.
Formation of gases in transformer oil: Mineral oils (transformer oil)
are composed of saturated hydrocarbons called paraffins, whose general molecular
formula is CnH2n+2 with n in the range of 20-40. The cellulosic
insulation material is a polymeric substance whose general molecular formula
is (C12H14(OH)6)n with n in the
range of 300-750. Gases are formed inside an oil-filled power transformer, in
that various gases begin forming at specific temperatures shown in Fig.
1.
Hydrogen and methane begin to form in small amounts around 150°C. Beyond
maximum points, methane (CH4), ethane and ethylene production goes
down as temperature increases. At about 250°C, production of ethane (C2H6)
starts. At about 350°C, production of ethylene (C2H4)
begins. Acetylene (C2H2) starts between 500 and 700°C.
In the past, the presence of only trace amounts of acetylene (C2H2)
was considered to indicate a temperature of at least 700°C had occurred;
however, recent discoveries have led to the conclusion that a thermal fault
(hot spot) of 500°C can produce trace amounts (a few ppm).
|
| Fig. 1: |
Gas generation chart |
|
Larger amounts of acetylene can only be produced above 700°C by internal
arcing. Between 200 and 300°C, the production of methane exceeds hydrogen.
Starting about 275°C and on up, the production of ethane exceeds methane.
At about 450°C, hydrogen production exceeds all others until about 750-800°C
then more acetylene is produced. It should be noted that small amounts of H2,
CH4 and CO are produced by normal aging. Thermal decomposition of
oil-impregnated cellulose produces CO, CO2, H2, CH4
and O2. Decomposition of cellulose insulation begins at only about
100°C or less. Therefore, operation of transformers at not >90°C
is imperative.
Faults will produce internal hot spots of far higher temperatures than these and the resultant gases show up in the DGA.
Solubility of gases in transformer oil: The solubilities of the fault gases in transformer oil as well as their temperature dependence are also important factors for consideration in fault gas analyses.
It should be noted that there are almost two orders of magnitude difference between the least soluble (H2) and the most soluble (C2H2) gas.
The majority of gases that are indicative of faults are also those that are in general the more soluble in the oil.
When the rates of gas generation are being followed, it is important to take
into account the solubility of these gases as a function of temperature (Fig.
2). Over a temperature range of 0-80°C some gases increases in their
solubility upto 79% while others decreases their solubility upto 66%.
Dissolved Gas Analysis (DGA): The DGA has become a popular technique
and is successfully used for many years. The method is very sensitive and gives
an early indication of incipient faults. The insulation oil used in sometimes
transformer leads to degradation of insulating transformer is long chain of
complex mixture of hydrocarbon compounds.
|
| Fig. 2 : |
Relative solubility (Y-axis) as function of temperature °C
(X-axis) |
|
Failures inside the produced remain in the insulating oil in dissolved state
and hydrocarbon compounds. Due to smaller molecular size, many of these compounds
are gasses. Types and quantity of hydrocarbon gases formed depends on the nature
and intensity of the fault. The gases so if concentration goes beyond saturation
level the gases come out and get collected in Bucholzs relay.
Due to dissolved gases in the transformer oil, the insulation property of this
oil goes weak and lead to transformer failures. The composition and quantity
of the gases generated depend on types and severity of the faults. Both these
kinds of information together provide the necessary bases for the evaluation
of any fault and the necessary remedial actions. Advantages that dissolved gas
analyses can provide:
| • |
Advance warning of developing faults |
| • |
Determining warning of the improper use of units |
| • |
Status checks on new and repaired units |
| • |
Convenient scheduling of repairs |
| • |
Monitoring of units under over load |
|
The regular monitoring of these dissolved gases interpret useful information
about the condition of the transformer and prior information of the faults by
observing the trend of the various gas contents. The relative distribution of
the gases is used to evaluate the origin of the production of these gases and
the rate at which the gases are formed to assess the intensity and propagation
of the gases. A diagnostic code; warnings of any gas concentrations, increments,
rates of change or ratios that exceed standard limits and short interpretive
remarks and recommendations become proper fault diagnosis. Supported diagnostic
methods for transformer DGA include the Duval triangle method and the Rogers,
Doernenburg and CIGRE gas ratio diagnostics. The main Interpretation methods
in fault diagnosis of power transformers used are:
| • |
The IEC-60599, 1999 |
| • |
The IEEE methods (Dornenburg, Rogers and key gas methods) |
| • |
The Duval triangle |
| • |
The IS: 10593 (2006) and IS: 9434 (1992) (Bureau of Indian Standards) |
| • |
It also needs proper sampling method and can be referred: |
| • |
Doble reference book on insulating liquids and gases |
|
| Table 1: |
Key faults in power transformer |
 |
|
| • |
ASTM D 923: Standard practice for sampling electrical insulating
liquids |
| • |
ASTM D 3613: Standard practice for sampling electrical insulating oils
for gas analysis and determination of water content |
| • |
IEC 60475: Method of sampling liquid dielectrics |
| • |
IEC 60567: Guide for the sampling of gases and of oil from oil-filled
electrical equipment and for the analysis of free and dissolved gases |
| • |
IS: 1866 (2000): Code of practice for electrical maintenance and supervision
of mineral insulating oil in equipment (3rd revision) |
|
Key faults in power transformers (PC57.104/D3.3, 2008;
IEC 60599 {Ed.2.1}, 1999) shown in Table
1.
Duval triangle in dissolved gas analyses: Duval triangle method (Duval,
2003, 2008; Singh, 2008a,
b; Akbari et al., 2008;
Duval and Dukarm, 2005) shown in Fig.
3 developed empirically in early 1970s and is used by IEC (IEC
60599 {Ed.2.1}, 1999). It is based on the use of three gases methane (CH4),
ethane (C2H4) and acetylene (C2H2),
corresponding to the increasing energy levels of gas formation. About 1000 sample
test reports were collected from different utilities in India. Out of those
reports, with abnormal gas formations and interpreted faults (PC57.104/D3.3,
2008; IEC 60599 {Ed.2.1}, 1999) are separated with
suggested remedial actions. The dissolved gas analysis by Duval triangle involves
percentage of gas (CH4, C2H4 and C2H2)
ratios in graphical presentation:
Key faults presented in Duval triangle (Table 2).
How to use Duval triangle?: There are two different procedures to use
this Novel method:
| • |
By using total accumulated gas |
| • |
By using total increase between conjugative samples |
|
By the use of this method both the procedures indicate the same fault.
A procedure to use the Duval triangle: Graphical use of Duval triangle is very simple. Consider the three side of triangle in triangular coordinates (x, y and z) representing the relative proportion of CH4, C2H4 and C2H2, from 0-100% for each gas.
To find the faults graphically (manual), first calculate the percentage of
each gas as per Eq. 1-3. Then the draw the
lines CH4% quantity parallel to C2H2 line,
C2H4% quantity parallel to CH4 line and C2H2%
quantity parallel to CH4. Thus, drawn intersection of all three lines
would indicate the fault for the GA results in the transformer.
| Table 2: |
Key faults in Duval triangle |
 |
|
| Table 3 : |
Triangular coordinates for Duval triangle zones. |
 |
|
For example, Fig. 4 indicates a fault and such verification
of faults by Duval triangle (manual) DGA has been done (for >100 fault reported
transformers).
These results were verified with DGA interpretation for total dissolved combustible
gases by other procedures used by different utilities in India. Example: CH4
= 56 ppm, C2H4 = 55 ppm and C2H2
= 43 ppm, manually calculated result D2 shown in Fig. 4.
Software implementation of Duval triangle DGA carried out for the same samples
on MATLAB 7.4 and cross verified. Used software can be obtained on request.
This software is developed with the knowledge of computer graphics and by fixing
the points for fault zones coordinates (polygons) (Table 3).
To define each polygon, the defined points are converted to Cartesian coordinates
(Duval, 2002) for percentage of gases for type of fault.
|
| Fig. 4: |
Graphical analysis on Duval triangle responsible |
|
|
| Fig. 5: |
Software analysis on MATLAB |
|
Same example analysed by software on MATLAB-7.4 and provides the same result
D2 in Fig. 5.
RESULTS AND DISCUSSION
In this study, manual and software implementations of Duval triangle for DGA
provides the following results:
| • |
Duval triangle method for DGA fault interpretations in power
transformers is very simple (with three gases only) and consuming less time |
|
|
| Fig. 6: |
Comparative fault analysis for power transformers (India) |
|
| • |
This method has satisfied the fault diagnosis (both manual
and software implementation) >95% accurate than any other method of diagnostics |
| • |
Traces of one of the three gases can provide the quick fault diagnosis
to a little experienced worker on the power transformers |
| • |
This method always provides a diagnosis with a very low percentage of
wrong diagnosis |
| • |
Duval triangle representation also allows to follow graphically in a very
easy way and the evaluation of faults with time visually |
| • |
Software can be easily developed with a small knowledge of computer graphics
and any high level computer language (i.e., C, C++, Java, FOTRON, MATLABs,
etc.) |
| • |
DGA fault diagnostics by different interpretation diagnostic tools (used
by various organizations) proved that T3 is the maximum faults occurring
in power transformers in the existing environmental conditions and service
procedures followed in India |
|
A comparative chart from DGA fault reports is given in Fig. 6.
CONCLUSION
The results show that Duval triangle interpretation is a robust technique and does not require much expertise.
Software implementation for Duval triangle can be done on the computer with many high level languages. Also, it is found from existing fault diagnostics tools for Indian conditions, the maximum fault occurring is T3 (44%).