International Journal of Electrical and Power Engineering

Year: 2011
Volume: 5
Issue: 3
Page No. 150 - 156

Three-Dimensional Electric Field Analysis and Measurement Inside High Voltage Substations

Authors : Sayed A. Word, Samy M. Ghania and Essam M. Shaalan

Abstract: The exposure to electric field now-a-days is an integral part in the design area of electrical power apparatus and systems. Moreover, the electric field produced by power lines, busbars and all high voltage equipments inside High Voltage (HV) substations is receiving more and more concerns to guarantee the life insurance of workers inside these substations. Therefore, the possible effect of the electric field exposure raises the question of how electric fields are created and what effects they may have. Therefore, monitoring the electric field inside Air Insulated Substation (AIS) and Gas Insulated Substation (GIS) is achieved in this study. This study not only depict the electric field distribution inside AIS using Charge Simulation Method (CSM) in three Dimensional (3D) and many Matlab M-files modeling programs developed by the researchers but also measured it inside AIS under 500 and 220 kV busbars and inside GIS nearby the 500, 220 and 66 kV busbars. The simulation results of AIS are compared with the measured values and the simulation results are matched with the measured values with very small tolerance about 1.4% for 220 kV model and about 4.4% for 500 kV model.

How to cite this article:

Sayed A. Word, Samy M. Ghania and Essam M. Shaalan, 2011. Three-Dimensional Electric Field Analysis and Measurement Inside High Voltage Substations. International Journal of Electrical and Power Engineering, 5: 150-156.

INTRODUCTION

Monitoring the HV electrical power equipments for electric fields have improved considerably in recent years. During the last years, electric and magnetic fields have been considered more and more as environmental factors. The International Commission on Non-Ionizing Radiation Protection (1998) published the guidelines. In these guidelines, the limit values for the electric field of 50 Hz are 5 kV m-1 for the public exposure (general public period of stay is 24 h day-1) and 10 kV m-1 for the occupational exposure (occupational period of stay is 8 h day-1). In 2002, the IEEE standard was published in which the maximum permissible exposure for the public is 5 kV m-1 generally and 10 kV m-1 in power line right-of-way (IEEE Std., 2002).

In controlled environment, the maximum permissible exposure is 20 kV m-1 (Tzinevrakis et al., 2008). Therefore, the electric field calculation is one of the essential factors in the design and development of any electrical utilities. The electric field is usually calculated with the use of several numerical methods through a computer while the Charge simulation method is one of the numerical methods which are commonly used for engineering applications to compute successfully and accurately the electric field. Therefore, we use this method to simulate the electric field inside high voltage substations in three dimensional. In this thesis, we are going deeply to depict the electric field distribution inside HV electrical power substation while the electric field distribution under different voltage level busbars is simulated and measured inside these substations and the simulated results are compared with the measured values. Also, we are investigating the different parameters that control the electric field distribution inside HV substation by changing some of them as a case of study.

Substation description and system modeling: The selected 500/220 kV AIS is supplied by four 500 kV overhead transmission lines which are connected to the same main bus system. This substation has three identical 3-phase, 500 MVA, 500/220/11 kV power transformers installed inside it, each transformer is composed of three single phase transformers.

This substation has a simply 500 and 220 kV bus systems with 300 m long and 12 and 9 m height, respectively. Detailed modeling procedure and mathematical model with respect to the technical data were presented in the research (Shaalan et al., 2010; Shaalan, 2011). Quick view on these substations layout and their models are presented in Fig. 1-3.

Electric field calculation methodology for the models under study: The basic principle of CSM lies in replacing the surface charge of the conductor with a set of discrete fictitious charges located inside the conductor.

Fig. 1: 3D spatial model of 500 and 220 kV switchyard inside AIS

These fictitious charges generate the electric field of similar intensity and direction as the original conductors in the observed zone. For the present developed model, the fictitious linear charges are used for the modeling of the line conductors (phase conductors, main bus system and bypass system) with a certain arrangement (Shaalan et al., 2010; Shaalan, 2011).

Although, the type and position of these fictitious charges inside the conductors are specified in advance (Shaalan et al., 2010; Shaalan, 2011), their values are unknown and in order to determine the value of these fictitious charges of the number (ns) on the conductor with known potential (Vcon), a certain number (ncp) of contour points are selected where the condition (ns = ncp) is satisfied. The contour points are placed at the conductor surface where the boundary conditions given by potentials of the contour points equal to Vcon are satisfied (Vcp = Vcon).

After choosing the type of fictitious charges as linear finite line type and distributing them along the simulated conductors. The values of these discrete charges are determined by satisfying the boundary conditions in Eq. 1 at a selected number of contour points where the potential of these fictitious charges are taken as particular solutions of Laplace equation which governs the assessment of the electric field:

(1)

Where:

[Q] = A column vector of the fictitious simulation charges
[V] = A column vector of the potential given by the boundary conditions
[P] = The matrix of the Maxwell potential coefficients (Kuffel et al., 2001; Malik, 1989)

Consider a finite line charge with constant charge densities (Total charge Qj) of length (d) with both ends at (X1-Z1) as end point and (X2-Z2) as starting point as shown in Fig. 4, then the potential coefficient (Pij) at any point Pi (X-Z) due to this charge and its image charge (Qj) with respect to the plane is given as following:

(2)

Where:


Fig. 2: Block diagram describing the analyzed GIS

Fig. 3: The considered 500 kV switchyard model of AIS to calculate the electric field inside it

After the calculation of the values of these charges then use the value of these charges to calculate the electric field strength produced by these fictitious charges. The expression for the Field coefficients (F) in the x-z directions due to this finite line charge (Qj) and its image charge (-Qj) at any point (Pi) are given as following:

(3)

Fig. 4: Finite line charge with constant charge densities; total charge Qj and contour point Pi in three dimensional; in x-z directions

(4)

(5)

Where:

Therefore, the net field (Ei) at any point (Pi) due to a number of individual charges (n) each with charge of Qj is given as:

(6)

Where (Fij)x, (Fij)y and (Fij)z are the field intensity or field coefficients and ax-az are unit vectors in the x-z directions, respectively (Akazaki and Mishijima, 1978). We should be noted that after the calculation of the electric field produced by these fictitious charges, we should check the accuracy of the calculation of the electric field using the surface error.

But if it isn’t meeting with the required accuracy of the calculation, you should change one of the following: the proper selection for the types of simulated charges (point, finite line, infinite line) and the suitable arrangement of these charges and contour points.

And then repeat these steps for many numbers of iteration till the accuracy of the calculation of the electric field using the surface error is meeting with the required accuracy of the calculation. Therefore, the calculation period of the simulation depends on the size of the boundary problems and the number of iterations till the required accuracy obtained. After the calculation of the electric field strength in a 3-phase system of sinusoidal low-frequency voltages, the root mean square values of the electric field strength are obtained which are proportional to the rms values of the voltages at all conductors. Finally, the CSM equations mentioned above are generalized in the form of many Matlab M-files programs with the same sequence to simulate and depict the electric field distribution inside the investigated substations.

RESULTS AND DISCUSSION

Steady state operation or normal operation: Within the HV investigated substations, the calculation of 3D electric field strength inside it and in its vicinity was performed in the 500 and 220 kV switchyards area (300 m along the bus length x 40 m around it; 20 m left and 20 m right) and the simulation results are shown as in Fig. 5 for 500 kV switchyard and in Fig. 6 for 220 kV switchyard. From Fig. 5 and 6, outline the zones where the 10 kV m-1 professional exposure limit is exceeded, it is found that the highest values occurs under the 500 kV busbars (13.5 kV m-1) under the connection conductors between 500 kV busbars and power transformers. This is because of the circuit breakers and the disconnecting switches make the 500 kV potential to go down to 6.5 m above the ground. On the 220 kV side of the substation, there are quit small areas which under the circuit breakers and disconnecting switches (reclosers).

It should be noted that the above 3D calculations are performed when all incoming and outgoing feeders are turned on at spacing between the phases of 6 m for 500 kV system and 4 m for 220 kV system and at height level of calculation of 1 m (the base case of the study).

Changing the space between the phases: As shown in Table 1 and Fig. 7, we are noticed that the decreasing of the space between the phases will cause the maximum value of the calculated electric field strength is decreased because the cancellation factor is increased while the increasing of the spacing between the phases will increase the maximum value of the calculated electric field strength because of the decreasing of the cancellation factor.

Fig. 5: The electric field distribution inside 500 kV switchyard of AIS

Table 1: The effect of changing the space between the phases on the calculated electric field

Table 2: The effect of changing the height level of calculation on the calculated electric field

Table 3: The effect of switching on/off one or more feeders on the calculated electric field

Fig. 6: The electric field distribution inside 220 kV switchyard of AIS; a) base case at space of 6 m, bus height of 12 m; b) at space of 6.2 m and c) at space of 5.8 m

But we should be noted that while decreasing the space between the phases, it should keep the insulation between the phases with stated values by national standards for each operating voltage to prevent the breakdown occurrence.

Changing the height level of calculation: From Fig. 8 and Table 2, we are noticed that as the height level of calculation is increased, the maximum value of the calculated field strength is increased because of closing from the live parts.

This meaning also that as the height level for supporting the live conductors (busbars, incoming feeders and outgoing feeders) increased, the maximum value of the calculated field strength is decreased because of the distance from the live parts.

Changing the load condition: From the given Table 3, we can note that as the middle incoming feeder is switched off the maximum electric field value is increased by 3.72% from base case; this is due to the reduction in the contribution of this feeder in the field cancellation factor. Besides that when all outgoing feeders are put off the maximum electric field value is increased by 24.75% from base case, this because the contribution of cancellation factor from all these lines are stopped and consequently a higher electric field value is obtained.

Fig. 7: The electric field distribution due to changing the space between the phases; a) at bus height of 12.2 m and b) at bus height of 11.8 m

Fig. 8: The electric field distribution due to changing the height level of supporting the conductors

Fig. 9: The longitudinal electric field profiles measured under 500 kV (phase A-C)switchyard inside cairo 500 substation at level 1 m

The measurement of the electric field inside HV substations: The electric field measurements are performed in this study at 1 m above the ground surface and underneath the 500 and 220 kV switchyards of AIS beside its measurement inside GIS nearby the 500, 220 and 66 kV busbars with 0.5 m. The measurement of electric field is performed using an advanced field meter; HI 3604 ELF survey meter (Holaday Industries, 2002). Outlines the longitudinal electric field profiles measured under different phases of 500 kV switchyard inside the substation as shown in Fig. 9. From Fig. 9, it is noticed that the maximum electric field value due to the different 3-phases is 22.9 kV m-1 and occurs at position x = 190 m along the busbar length and located under phase C of 500 kV busbar. Therefore, we can note that the electric field measured values are decreased as nearby from the 500 kV switchgear due to the increasing of the field cancellation factor. The maximum calculated value of electric field strength is 23.9 kV m-1 while the maximum measured value is 22.9 kV m-1, therefore the simulation results are matched with the measured values with very small tolerance (about 4.4%) which is due to the field meter used in the measurements is dependent on the natural of place where the electric field is measured. Also, the measured values inside GIS showed that the value of the electric field does not exceed the maximum permissible limit while its value not exceeds 2 V m-1 inside insulated switchgear rooms.

CONCLUSION

Following the electric field distribution inside AIS, there are large areas especially in the 500 kV switchyard where the electric field intensity is >10 kV m-1; exceeds the professional exposure limit and when following the electric field distribution inside GIS, it is found that the electric field intensity is very quit small and not exceeds the professional exposure limit inside the switchgear rooms but the highest values have been found in the neighborhood of the incoming 500 kV transmission lines which are not encapsulated inside enclosures filled with SF6 where the electric field strength under these lines reaches values up to 22.5 kV m-1; exceeds the professional exposure limit. The calculated and measured electric field around the fence of the substation is separated into three areas. In area I, the field is <5 kV m-1, area III has <10 kV m-1. The maximum is in the area II under the 500 kV transmission lines which is greater than the limit for 24 h exposure time for humans. Therefore, the results presented show that the professional human exposure limit to the electric field is significantly exceeded in several areas of AIS especially under the 500 kV lines, busbars and around the power transformers.

RECOMMENDATIONS

Therefore, the electric field strength can be decreased to meet the national standards reference exposure levels by one from the following:

Increasing the height level of busbars, incoming feeders and outgoing feeders (live conductors) for example, particularly in 500 kV substations with proposed 12 m busbar height. If the ICNIRP levels are not met, the busbar height has to be increased to 14 m with significant cost implications
Decreasing the space between the phases of busbars, incoming feeders and outgoing feeders (live conductors) but with a limit value to insure the insulation between them and prevent the occurrence of breakdown
The live conductors (busbars, incoming feeders and outgoing feeders shall be housed in separate metal enclosed modules called metal-clad switchgear which filled with a superior dielectric gas; sulfur hexafluoride (SF6)